The ETP thermostat is an allround ON/OFF thermostat for industrial use.
4 temperature ranges from –50 to +375ºC Change-over between cooling and heating functions Several thermostats may be controlled by 1 sensor DC outputs, 0-10V and 0-20/4-20mA Safeguarded in case of sensor failure May be applied as a value converter
Product Range
| Type |
Product |
EAN-Nr |
| ETP-1970 |
230V, Output 0-20mA |
|
| ETP-1974 |
230V, Output 4-20mA |
|
| Accessories |
|
|
| ETPD-97 |
Analogue instrument |
|
| ETPP |
Ext. potentiometer unit |
|
| ETF-..97 |
Temperature sensor of various types |
|
Temperature scales, set at installation: 4 temperature scales are supplied to be attached to the control knob. Scale 1: -50/+75ºC Scale 2: +50/+175ºC Scale 3: +150/+275ºC Scale 4: +250/+375ºC
FUNCTION The ETP-97 thermostat is equipped with 6 switches and a programming table, which facilitates the choice between the following functions and settings:
1. The relay action may be set to call for either "heating" or "cooling".
2. There are 4 temperature ranges from -50ºC to +375ºC selectable with an interval of 125ºC.
3. Adjustment for "master-slave function", i.e. the master thermostat sensor controls one or several slave thermostats. The system allows an application as a neutral-zone thermostat, a 2- to 3-step thermostat, with several alarm levels etc.
Controls The set control serves to set the desired temperature. With a coin inserted into its slot the scale may be adjusted in accordance with a reference thermometer. Thus, a high accuracy throughout the entire scale is ensured. The DIFF control enables the temperature differential to be adjusted from 1 to +15ºC. The SCALE ADJ control allows compensation for sensor tolerances and conductor resistance. Red light-emitting diode indicates when the relay has been connected. In case of an error in the sensor circuit, the output relay will always fall out.
Interconnections: An analogue instrument, type ETPD, may be connected to display the sensor temperature. Voltage outputs 0-10V DC and current outputs 0-20mA or 4-20mA may be utilized for remote control and data transfer to PLC systems etc. These outputs also allow the application of the ETP-97 thermostat as a value amplifier (temperature transducer) within a larger system. The setpoint may be controlled externally via External Potentiometer, type ETPP.
Technical data
| Power consumption |
3V A |
| Ambient temperature |
-20/+50ºC |
| Accuracy |
±1ºC |
| Relay output |
1 S.P.C.O., max. 10A, 250V resistive |
| Expected lifetime |
2X10 switch functions at max. load |
| DC output |
0-10V DC, Max. 1mA Min. range = 0mA U = 80mV/ºC |
| Current output ETP-1970 |
0-20mA current loop I = 160µA/ºC |
| Current output ETP-1974 |
4-20mA current loop I = 128µA/ºC |
| Dimension & weight |
Din rail mounting. Width 52.5mm and height above rail max. 56mm. |
| Weight |
180g |
|