HVAC CONTROLS & POWER
 
 

Electronic Thermostat - ETP
The ETP thermostat is an allround ON/OFF thermostat for industrial use.
 
PTC sensor for temperature measurement
Compensation for sensor tolerances and wire resistance
Several thermostats may be controlled by 1 sensor
DC outputs for external regulation by PLC control
Safeguarded in case of sensor failure
 
Product Range
Type Product EAN-Nr
ETP-1951 230V, -30 to +30°C  
ETP-1952 230V, 10 to +110°C  
ETP-1953 230V, 0 to +40°C  
 
Accessories
 
ETPD-x Analogue instrument available in 3 different scales  
ETPP Ext. potentiometer unit for panel mount  
ETF-..95 Temperature sensor of various types  
 
UNITEMP FAMILY CONCEPT:
UNITEMP is a designation for a series of electronic thermostats for regulation and monitoring of cooling and heating installations as well as industrial plants where accurate regulation is desired.
The UNITEMP units make use of the same types of sensors and accessories. An external control unit ETPP may control 1 or 2 thermostats simultaneously, and regulation by external DC signal is possible, eg from a PLC control. The units are installed on DIN rails.
 
FUNCTION
The ETP-97 thermostat is useful for heating or cooling function.
3 types cover scale ranges from -30°C to +110°C. Temperature differences may be set by the control knob DIFF.
A light diode lights up, when the relay is energized.
 
Controls
The SET control serves to set the desired temperature. With a coin inserted into its slot the
scale may be adjusted in accordance with a reference thermometer. Thus, a high accuracy
throughout the entire scale is ensured. The DIFF control enables the temperature differential
to be adjusted from 0,3 to 10% of the scale range.
The SCALE ADJ control allows compensation for sensor tolerances and conductor
resistance. In case of an error in the sensor circuit, the output relay will always fall out.
 
Interconnections:
An analogue instrument, type ETPD, may be connected to display the sensor temperature.
Voltage outputs 0,5 to 5,5 VDC may be utilized for remote control and data transfer to PLC systems etc.
 The setpoint may be controlled externally via External Potentiometer, type ETPP.
 
Technical data  
Power consumption 3V A
Ambient temperature -20/+50ºC
Accuracy ±1ºC
Relay output 1 S.P.C.O., max. 10A, 250V resistive
Expected lifetime 2X10 switch functions at max. load
DC output 0,5-5,5V DC, Max. 20mA
Dimension & weight Din rail mounting.
Width 52.5mm and height above rail
max. 56mm. Weight 190g