2-Step Thermostat - ETT-2
Industrial 2-Step thermostat for ON/OFF regulation.
 
PTC sensor for temperature measurement
Compensation for sensor tolerances and wire resistance
Several thermostats may be controlled by 1 sensor
DC outputs for external regulation by PLC control
Safeguarded in case of sensor failure
 
Product Range
Type Product - add K to type no for cooling version EAN-Nr
ETT-2-1951  230V, -30/+30ºC  
ETT-2-1952  230V, +10/110ºC  
ETT-2-1953  230V, 0/+40ºC  
 
Accessories
 
ETPD-x Analogue instrument available in 3 different scales  
ETPP Ext. potentiometer unit for panel mount  
ETF-..95 Temperature sensor of various types  
 
UNITEMP FAMILY CONCEPT:
UNITEMP is a designation for a series of electronic thermostats for regulation and monitoring of cooling and heating installations as well as industrial plants where accurate regulation is desired.
The UNITEMP units make use of the same types of sensors and accessories. An external control unit ETPP may control 1 or 2 thermostats simultaneously, and regulation by external DC signal is possible, eg from a PLC control. The units are installed on DIN rails.
 
FUNCTION
For ON/OFF regulation of cooling/heating plants in two steps.
Available for cooling or heating function.
3 types cover a scale range from –30 to +110ºC. Equipped with two S.P.S.T., 6A.
The distance between activation of relay 1 and relay 2 may be adjusted from 0-10% of the scale range with the help of control knob DIFF:
 
Controls
The SET control serves to set the desired temperature. With a coin inserted into its slot the scale may be adjusted in accordance with a reference thermometer. Thus, a high accuracy throughout the entire scale is ensured.
The DIFF control enables the temperature differential
to be adjusted from 0,3 to 10% of the scale range.
The SCALE ADJ control allows compensation for sensor tolerances and conductor resistance.
In case of an error in the sensor circuit, the output relays will always fall out.
 
Step distance:
Scale range / Type Adjustable distance Step difference
-30/+30ºC 0/+6ºC 0,5ºC
10/110ºC 0/+10ºC 0,8ºC
0/+40ºC 0/+4ºC 0,3ºC
 
 
Technical data  
Power consumption 3V A
Ambient temperature -20/+50ºC
Accuracy ±1ºC
Relay output 2 S.P.S.C., max. 6A, 250V resistive
Expected lifetime 2X10 switch functions at max. load
DC output 0,5-5,5V DC, Max. 20mA
Dimension & weight Din rail mounting.
Width 52.5mm and height above rail
max. 56mm. Weight 190g
Interconnections:
An analogue instrument, type ETPD, may be connected to display the sensor temperature.
Voltage outputs 0,5 to 5,5 VDC may be utilized for remote control and data transfer to PLC systems etc.
The setpoint may be controlled externally via External Potentiometer, type ETPP.
Relay functions:
Cooling function:
At calls for cooling, the relays are activated stepwise.
Relay 1 is activated first. Green LEDs are lit.
Heating funktion:
At calls for heating, the relays are activated stepwise.
Relay 2 is activated first. Red LEDs are lit.